Siemens S7 PLC Simulator
ISO-on-TCP simulator that speaks S7comm well enough for a real session: connect confirm, PDU length negotiation, and read requests served out of a drifting DB1, with the absolute address syntax documented.
What you'll learn: an S7comm source that reads a data block by absolute address, a Lua frame parser, and a generated Data Grid dashboard.
Prerequisites: Serial Studio Pro and Python 3 for the simulator.
Overview
This project exercises Serial Studio's Siemens S7 client against a simulated CPU. The companion script is an ISO-on-TCP server that speaks just enough S7comm for a real session: it answers the class-0 connect request with a connect confirm, negotiates the message budget, and serves read requests out of one data block whose four values drift over time.
Nothing about the client is stubbed. The same handshake, the same PDU length negotiation and the same read service run against the simulator as against an S7-1500 in a cabinet.
S7 support needs a Serial Studio Pro license. See serial-studio.com for details.
Requirements
Python 3 standard library only. No snap7, no vendor DLL.
Running the simulator
The bundled S7 PLC Simulator.ssproj starts the simulator for you. Its Control Loop launches
s7_plc_simulator.py on 127.0.0.1 the moment you press Connect, and Serial Studio stops the
helper again when you disconnect, change project, or quit. Open the project and connect; there is
nothing to run by hand.
One caveat comes from the protocol itself. The ISO-TSAP port is fixed at 102, and ports below 1024 are privileged on macOS and Linux, so unless Serial Studio is running with elevated privileges the auto-started helper cannot bind port 102 and the connection reports no CPU. Start the simulator by hand once before connecting when that happens:
sudo python3 s7_plc_simulator.py
Windows does not reserve low ports, so the auto-start binds 102 from an ordinary session; run it by hand from an Administrator prompt only if you prefer to:
python s7_plc_simulator.py
Flags:
| Flag | Effect |
|---|---|
--host ADDR |
Listen address (default 127.0.0.1; use 0.0.0.0 to reach it from another host). --bind is an accepted alias. |
--port N |
Listen port (default 102). Serial Studio always dials 102, so this is only useful when driving the simulator from another script. |
--rate HZ |
Simulation update rate (default 10 Hz). |
Address space
The simulator serves one data block, DB1, eight bytes wide:
| Address | Type | Name | Behaviour |
|---|---|---|---|
DB1.DBD0:REAL |
REAL | Tank_Level | Slow sine between 15 % and 85 %, plus noise |
DB1.DBW4:INT |
INT | Motor_Speed | Ramps toward 1450 RPM or 0 RPM |
DB1.DBX6.0 |
BOOL | Pump_Running | Trips occasionally |
DB1.DBB7 |
BYTE | Cycle_Counter | Wraps every 256 simulation steps |
Everything else is refused with the return code a real CPU sends for an address that does not exist, so a typo in the variable list shows up in the pane rather than as a plausible-looking zero.
Address syntax
Serial Studio accepts the two absolute forms the S7 world writes, both case-insensitive:
| Form | Meaning | Example |
|---|---|---|
DB<n>.DB{X,B,W,D}<byte>[.<bit>] |
Data block | DB5.DBD20, DB1.DBX0.3 |
{I,E,Q,A,M}{X,B,W,D}<byte>[.<bit>] |
Process image and flags | MW10, IB0, Q0.1 |
E and A are the German spellings of I and Q. The width letter picks the type when nothing
else says otherwise:
| Letter | Width | Implied type |
|---|---|---|
X |
1 bit | BOOL |
B |
1 byte | BYTE |
W |
2 bytes | WORD (unsigned) |
D |
4 bytes | DWORD (unsigned) |
An optional :TYPE suffix overrides how the bytes are rendered, as long as it fits the width:
| Address | Reads as |
|---|---|
DB1.DBD0 |
DWORD, unsigned 32-bit |
DB1.DBD0:REAL |
REAL, IEEE-754 single precision |
DB1.DBD0:DINT |
DINT, signed 32-bit |
DB1.DBW4 |
WORD, unsigned 16-bit |
DB1.DBW4:INT |
INT, signed 16-bit |
DB1.DBB0:STRING[32] |
S7 STRING, 32 characters |
This matters for the bundled project: DB1.DBD0 alone would read the level as a 32-bit unsigned
integer full of float bits, which is why the variable is spelled DB1.DBD0:REAL.
Rack and slot
The rack and slot select the CPU inside the rack; a wrong pair is refused by the CPU at the ISO connect step, not later.
| Family | Rack | Slot |
|---|---|---|
| S7-300, S7-400 | 0 | 2 |
| S7-1200, S7-1500 | 0 | 1 |
| LOGO!, S7-200 SMART | 0 | 0 |
The simulator accepts any rack and slot and prints what it was asked for, so both settings can be tried without hardware.
Real hardware
Two CPU settings have to be right or every read comes back refused, whatever the addresses say:
- PUT/GET access must be enabled. In TIA Portal: CPU properties, Protection & Security, tick Permit access with PUT/GET communication from remote partner. Without it the CPU answers the read job with an access-denied error class, which Serial Studio reports as "the controller denied access; check PUT/GET and optimized block access".
- Optimized block access must be off for the blocks you read. Right-click the data block,
Properties, untick Optimized block access, then recompile and download. An optimized block
has no absolute byte offsets, so
DB1.DBD0addresses nothing.
Both are TIA Portal settings on the S7-1200/1500 families. Classic S7-300/400 blocks are always non-optimized, and PUT/GET is allowed by default.
Create Project from Variables
-
Start the simulator.
-
Pick Siemens S7 as the Connection.
-
Set Host to
127.0.0.1, Rack to0, Slot to1. -
Press Configure Variables… and add:
Name Address Tank_LevelDB1.DBD0:REALMotor_SpeedDB1.DBW4:INTPump_RunningDB1.DBX6.0The dialog validates each address as you type and refuses one that does not parse, so a bad spelling never reaches the CPU.
-
Press Create Project from Variables. The Project Editor opens with one group per memory area (here just
DB1), a plot for each numeric variable and an LED for the bit. -
Save it, close the editor, and press Connect.
Or open the bundled S7 PLC Simulator.ssproj, which is that generated project with units filled
in.
The variable list is frozen while a session is live: the wire layout is sized when the poll worker is configured, so adding a variable means disconnecting first.
Command line
SerialStudio --s7 127.0.0.1 --s7-rack 0 --s7-slot 1 \
--s7-variable "DB1.DBD0:REAL:Tank_Level" \
--s7-variable "DB1.DBW4:INT:Motor_Speed" \
--s7-variable "DB1.DBX6.0:Pump_Running"
A --s7-variable spec reads address[:name]. The address may itself carry a :TYPE suffix, so
the parser takes the longest leading prefix that validates as an address and treats the rest as
the name.
Files
s7_plc_simulator.py: the ISO-on-TCP / S7comm simulator.S7 PLC Simulator.ssproj: ready-made project for the three variables above.README.md: this file.
Notes
- The driver polls; it never writes. Writing controller memory is out of scope for this driver, so a read-only user account on the CPU is enough.
- Values are latched: only variables whose value moved are published on a tick, so a stalled process produces no frames rather than a stream of identical rows.
- If the connection is refused with "the controller refused the ISO connection", the rack or slot is wrong. If it opens but every variable reports "access denied", it is PUT/GET or optimized block access.
- Add
DB1.DBB7as a fourth variable to watch the simulator's cycle counter; the simulator serves it already.